Design, EPC, integration and O&M for factories, hospitals, campuses and commercial buildings.
Battery energy storage
As pioneers in battery storage, we design, integrate, install and maintain BESS for factories, commercial sites, solar plants and grid projects, from single cabinets to multi-MWh containers.
What a battery does
Most sites combine several of these jobs, and the energy management system (EMS) decides which comes first.
Trim the 15-minute maximum demand you're billed on; the saving depends on your contract demand.
Charge in cheaper hours and discharge in the tariff's peak windows.
Store midday solar and use it after sunset instead of exporting or curtailing it.
Cover short outages and light loads, so the genset starts less often.
Keep critical loads running through outages and dips, where the system is designed to island.
With spare PCS capacity, supply reactive power and smooth fast load swings.
Let fast chargers draw short bursts from the battery instead of the grid connection.
We don't publish savings percentages; we work them out from your own bills and meter data.
Tamil Nadu tariff
Tamil Nadu's HT tariff adds 25% in the two peak windows and takes 5% off overnight, so the battery charges off-peak and discharges into the peaks.
Rates set for FY2022-23 to FY2026-27, ending 31 March 2027; the next order may change them.
Source: TNERC, Tariff Order No. 6 of 2025 (opens in a new tab) (30 June 2025, effective 1 July 2025).
Inside a BESS
Cells store the energy; the other parts keep it safe, convert it and decide when to use it.
Lithium iron phosphate (LFP) cells of about 3.2 V each, where the energy is stored.
Cells in series with busbars, sensors and a module BMS.
Modules in series with a rack BMS, fuse and contactor.
Watches voltage, current and temperature, balances cells and trips on limits.
Racks plus cooling, detection, suppression, venting and an emergency stop.
The two-way inverter between the battery's DC and your AC network.
Connect the PCS to your LT or HT network, with protection relays.
Decides when to charge and discharge, and talks to meters, solar, gensets and chargers.
Formats & chemistry
All-in-one units of a few hundred kWh each, paralleled for more. Suits factories, hospitals and campuses.
Multi-MWh containers with separate PCS and transformer skids. Suits large plants, solar farms and grid projects.
The battery has its own inverter on your AC network: the usual way to add storage to existing solar.
Battery and solar share one inverter. Suits new hybrid plants and captures solar that would be clipped.
Source: NREL (now NLR), Evaluating the Technical and Economic Performance of PV Plus Storage Power Plants (opens in a new tab) (August 2017).
Lithium iron phosphate (LFP) is the default for stationary storage: long cycle life, good thermal stability and no cobalt or nickel. It made up over 90% of stationary storage installed worldwide in 2025.
Source: IEA, Global EV Outlook 2026: Electric vehicle batteries (opens in a new tab) (2026).
Safety
Good design makes faults unlikely, catches them early and stops them spreading. The CEA's BESS safety chapter applies from 1 April 2027.
Qualified LFP cells, cell-level BMS monitoring and a two-fault-tolerant design.
Monitored smoke, gas, heat and flame detection, with door and ventilation alarms.
Automatic fire suppression in every battery container.
Forced ventilation with automatic louvres, and shutdown if ventilation fails.
Spacing between enclosures, fencing at least 1.8 m high, CCTV and intrusion alarms.
Emergency stops and an independent fire-safety audit, as the CEA requires, plus an emergency plan shared with the local fire service.
The chapter covers BESS connected above 650 V; we design smaller systems the same way.
Source: CEA, CEA (Measures relating to Safety and Electric Supply) Amendment Regulations 2026 (opens in a new tab) (Gazette, 30 March 2026).
Standards
Certification belongs to the equipment maker, not to us: we specify certified equipment, check its test reports and commission to these methods.
| Level | Standards | What it covers |
|---|---|---|
| Cell & battery | IEC 62619 (+ IEC 63056) or UL 1973 | Lithium cell and battery safety |
| System | UL 9540 or IEC TS 62933-5-1 + IEC 62933-5-2 | Whole-system safety |
| Fire test data | UL 9540A | Fire test method, not a certification |
| Performance tests | IEC 62933-2-1 (IS 17067 Part 2/Sec 1) | Energy and efficiency, tested yearly |
| Installation practice | NFPA 855 (2026 edition) | Installing stationary storage |
| India | CEA Safety & Construction amendments 2026 | Binding from 1 April 2027 |
Performance
Measured at the meter including auxiliaries, as the CEA's 2026 standards define it (minimum 70%).
The CEA's minimums are 90%, 80% and 70% of output at 5, 10 and 15 years; we plan augmentation where needed.
We size for the energy you need delivered; the CEA's minimum depth of discharge is 80%.
We check the maker's warranty terms and line our commitments up with them.
Source: CEA, Technical Standards for Construction of Electrical Plants and Electric Lines (Amendment) Regulations, 2026 (opens in a new tab) (Gazette, 23 June 2026).
Scale
Design, EPC, integration and O&M for factories, hospitals, campuses and commercial buildings.
New hybrid plants, and storage added to existing rooftop, captive and ground-mount solar.
Owner's engineering, FAT witnessing, balance-of-plant, commissioning and O&M for grid-connected storage in southern Tamil Nadu.
Illustrative. Schematic, not to scale.
Ways to pay for storageExisting systems
From 1 April 2027, the CEA's safety chapter applies to batteries connected above 650 V, including an independent fire-safety audit.
We check your system and records against the chapter and list the gaps.
See our consulting servicesWe gather the documents and test records the auditor will ask for. We don't act as the auditor.
A baseline inspection and capacity test, then an AMC.
How O&M takeovers workSource: CEA, CEA (Measures relating to Safety and Electric Supply) Amendment Regulations 2026 (opens in a new tab) (Gazette, 30 March 2026). Regulations 122(M) and 122(N).